Campground Electrical Compatibility Checker
Will your RV's electrical load actually fit the campsite's shore power? This free tool checks what you plan to run against your RV's cord rating and the site's service — modeling 50A service correctly as the two separate 120V legs it really is, not a simplified single number.
HomeAway Camping serves Katy, Brookshire, Sealy, Hempstead, Waller, Fulshear, and the greater West Houston area from shop locations in Katy and Brookshire, Texas, with mobile service available across the standard service area.
Check Your Load
Leg A
--
Leg B
--
Texting not supported on this device? Call (832) 859-9850.
How this is calculated
50A service is two separate 120V legs — not a single 50A × 120V number. Each leg can deliver up to its own rated amps at 120V; a circuit wired to one leg can never borrow capacity from the other leg.
Adapters never add capacity — connecting a mismatched cord and pedestal limits you to the smaller of the two ratings. Adapting a 50A RV down to a 30A pedestal collapses you to just ONE working 120V leg; whichever of your RV's circuits are wired to the other leg get no power at all until you're back on full 50A service.
Continuous-load derating: a leg is flagged "caution" once its load passes 80% of that leg's capacity — a standard general electrical-code convention for sustained loads, leaving headroom before the hard limit.
Overload: a leg's total must never exceed that leg's full rated capacity — this is a hard rule, not a judgment call.